OVERVIEW
The EG71 solves a common integration headache: modern buildings run a mix of wired and wireless protocols, and getting them talking to one system usually means multiple gateways, converters and cabling runs.
EG71 handles it with one device. It brings LoRaWAN®, Modbus RTU/TCP, BACnet/IP, KNX and M-Bus onto a single gateway, so field devices across HVAC, energy monitoring, lighting and building automation systems report through one point of integration.
Processing happens locally. Built-in edge computing runs configurable logic on-site, so control decisions don’t depend on a live cloud connection, and response times stay fast even if the network drops out.
Connectivity is flexible by design. Ethernet, 4G, RS485 and digital I/O interfaces mean EG71 connects to a wide range of field devices, whether you’re retrofitting an existing building or specifying for new construction.
Once configured, EG71 connects building data to the cloud for remote monitoring and management, giving facility teams visibility without needing to be on-site.
Backed by OneTemp’s local expertise, EG71 is a practical, scalable option for integrators and building managers who need multi-protocol reliability without adding hardware complexity.
-
SPECIFICATIONS
Hardware System
CPU Quad-core 1.5 GHz, 64-bit ARM Cortex-A53 Memory 2GB DDR4 RAM Flash 32 GB eMMC Extendable Storage 1 × Micro SD Slot LoRaWAN
Antenna 1 × 50 Ω SMB – Female External Connector Channel 8 (Half-duplex) Frequency Band CN470/IN865/EU868/RU864/US915/AU915/KR920/AS923-1&2&3&4 Sensitivity -140dBm Sensitivity @292bps Tx Power 27dBm Max Protocol V1.0 Class A/Class B/Class C and V1.0.2 Class A/Class B/Class C LBT Support Number of Devices Around 2000 Devices (based on 10 min uplink interval) Advanced Features Noise Analyser, Gateway Fleet, Multicast, FUOTA Ethernet Interface
Port 2 × RJ45 Ports (WAN/LAN Software Switchable) Physical Layer 10/100/1000 Base-T (IEEE 802.3) Data Rate 10/100/1000 Mbps (Auto-Sensing) Interface Auto MDI/MDIX Mode Full/Half Duplex (Auto-Sensing) Ethernet Isolation 1.5 kV RMS PoE 1 × 802.3 af PoE PD on ETH1 Port Wi-Fi Interface
Antenna 1 × 50 Ω SMB – Female External Connector Standards IEEE 802.11b/g/n, 2.4 GHz Tx Power 802.11b: 18 dBm +/-2.0 dBm (11 Mbps)
802.11g: 18 dBm +/-2.0 dBm (6 Mbps)
802.11g: 17 dBm +/-2.0 dBm (54 Mbps)
802.11n@2.4 GHz: 17 dBm +/-2.0 dBm (MCS0_HT20)
802.11n@2.4 GHz: 16 dBm +/-2.0 dBm (MCS7_HT20)
802.11n@2.4 GHz: 17 dBm +/-2.0 dBm (MCS0_HT40)
802.11n@2.4 GHz: 16 dBm +/-2.0 dBm (MCS7_HT40)Mode AP or Client mode Security AP: WPA-PSK/WPA2-PSK authentication, WEP/TKIP/AES encryption
Client: WPA-PSK/WPA2-PSK/WPA-Enterprise/WPA2-Enterprise
authentication, WEP/TKIP/AES encryptionCellular Interface (optional)
Network 4G LTE(CAT1)/GSM Tx Power Class 3 (23 dBm ±2 dB) Antenna 1 × 50 Ω SMB – Female External Connector Cellular Band L08GL (Global except North America):
LTE-FDD: B1/2/3/4/5/7/8/12/13/17/18/19/20/25/26/28/66
LTE-TDD: B34/38/39/40/41;
GSM: B2/3/5/8
L09NA (North America):
LTE-FDD: B2/4/5/12/13/66SIM Slot 1 (Nano SIM-4FF) Data Interfaces
RS485
Numbers 2 × RS485 Baud Rate/bps 1200/2400/4800/9600/19200/38400/57600/115200 (Software Switchable) Terminal Resistor 1 × 120 Ω Terminal Resistor (Software Switchable) Number of Devices Up to 128 Devices per RS485, total 256 Devices KNX
Numbers 1 × KNX/TP1 Bus Voltage 21-30 V DC, via the KNX bus Baud Rate 9600 Number of Devices Up to 63 Devices M-BUS (Under Development)
Numbers 1 × M-BUS Voltage 24-42V Maximum Current Load 10mA Baud Rate/bps 300/600/1200/2400/4800/9600 (Software Switchable) Number of devices Up to 20 Devices Universal Input
Numbers 8 × Universal Inputs (Software Switchable) Digital Input Work Mode: Digital Input (Wet Contact)
Load: 0-24V DCAnalog Input Input Type: 0-10V or 4-20mA
Resolution: 12bit
Accuracy: ±1% FSRTD Input Input Type: PT1000 or Ni1000
Input Connection: 2-wire
Accuracy: ±0.5°CNTC Input Input Type: NTC 10K Type 2, NTC 10k Type 3 or NTC 20k
Accuracy: ±0.5°C at 25°CResistance Input Input Type: 1000 Ω or 2000 Ω
Accuracy: 1 ΩDigital Input
Numbers 4 × Dry Contact Inputs Work Mode Digital Input, Pulse Counter Frequency >=1000Hz Digital Output
Numbers 3 × Relay Outputs Resistive load Max. 3A@30 V DC or 3A@110 V AC Analogue Output
Numbers 4 × Analog Outputs Analog Type 4-20mA or 0-10V (Software Switchable) Maximum Load 20mA Resolution 12 bit Accuracy ±1% FS Others
Screen 1.3-inch OLED Screen, 128 × 64 Pixels Screen Buttons 7 × Screen Control Buttons NFC 13.56MHz, support adding Milesight LoRaWAN® end devices Reset Button 1 × RST USB 1 × USB Type-C for Power Supply and Console LED Indicators 1 × SYS Power Connector 1 × 2-Pin Terminal Block Built-in Watchdog, RTC, Timer Software
Building Protocol Data Acquisition:
RS485: Modbus RTU, BACnet MS/TP
KNX: KNX/TP
Ethernet/Wi-Fi: BACnet/IP, Modbus TCP, Modbus RTU over TCP
Data Forwarding:
MQTT(s), HTTP(s), BACnet/IP, Modbus TCP, Modbus RTU over TCPEmbedded Network Server Built-in LoRaWAN® network server, support Gateway Fleet, Multicast, FUOTA features VPN Tunnel OpenVPN/IPsec/PPTP/L2TP/WireGuard Firewalls Access Control, DMZ, Port Mapping (DNAT), MAC Binding, Filtering
(IP&Domain)DDNS Supported 14 service providers, others can be configured manually Multilevel Authority Multiple Levels of User Authority Reliability Link Failover Diagnostic Tools Ping, Traceroute, Tcpdump, QXDM, Log Server Configuration Web, CLI (SSH/Telnet), On-demand dial up, SNMP Remote Management Milesight Development Platform Even Alarm Power On, Network Up/Down, VPN Up/Down, etc. App Python SDK, Node-RED, Docker Power Supply and Consumption
Power Input 1. 24 V DC/AC by Terminal Block
2. 802.3 af PoE
3. 5V/3A by USB Type-C Port1Power Consumption Typical 411mA@20V (8.2W), Maximum 562mA@20V (11.24 W) Physical Characteristics
Reliability MTBF > 500, 000 hours @ 25°C (according to Bellcore TR-332) -non contractual Ingress Protection IP30 Housing & Colour PC+Aluminium Alloy, Grey Weight 375.6g Dimensions 123 x 90 x 36 mm (4.84 x 3.54 x 1.42 in) Wire Connection AWG 24-16 Installation Wall Screw Mounting, DIN Rail Mounting Environmental
Operating Temperature -40°C to +60°C (-40°F to +140°F) Storage Temperature -40°C to +85°C (-40°F to +185°F) Relative Humidity 0% to 95% (non-condensing) at 25°C/77°F Approvals
Regulatory CE, CE (RED), FCC 1: When powered via USB, M-BUS and Universal Inputs will not work properly.
-
Connect EG71 to OneTemp IoT Cloud
EG71 pairs well with OneTemp IoT Cloud for teams who want local support alongside their monitoring platform. OneTemp IoT Cloud gives you real-time dashboards, automated alerts and long-term data logging, backed by the same team supplying the hardware. There’s no gap between vendor and platform support.
The platform includes pre-configured payload formatters for Milesight devices, so setup is fast, and it scales from a handful of sensors to a multi-site network without switching systems.
-
FAQ'S
What’s the biggest value of the EG71 for building integrators?
The EG71 cuts hardware and integration costs by replacing several point solutions with one gateway. Instead of running separate protocol converters, I/O modules and a LoRaWAN gateway, integrators get all three in a single device.
- Direct wired protocol access: BACnet, Modbus and KNX devices connect without extra converters
- Built-in I/O: digital and analog signals connect directly, no expansion modules needed
- Wireless integration: LoRaWAN® sensors run through the same gateway
- Local logic and control: edge processing handles automation and alarm logic on-site
- Flexible forwarding: data reaches BMS, SCADA or cloud platforms via MQTT, HTTP, BACnet or Modbus
For OneTemp customers, that means fewer devices on-site, simpler wiring and commissioning, and one local point of contact for support and stock.
Which building protocols does the EG71 support?
- Wired: BACnet/IP, BACnet MS/TP, Modbus TCP, Modbus RTU, KNX TP, and M-Bus (M-Bus support is under development, contact OneTemp for current status)
- Wireless connectivity: built-in LoRaWAN® network server for direct sensor management
- Northbound data forwarding: MQTT and HTTP for active data pushing, plus BACnet/IP and Modbus TCP for BMS or SCADA polling
This lets integrators connect wired equipment and wireless sensors through one gateway, process data locally, and forward it to whichever system needs it.
How is the EG71 different from a standard protocol converter or LoRaWAN gateway?
Most protocol converters handle one translation job. Most LoRaWAN gateways just connect sensors to a network server. The EG71 does both, plus local processing, remote management and developer tools, in one edge device. Fewer integration layers between field devices and your BMS or cloud platform, less hardware to spec, wire and maintain.
Can the EG71 replace Niagara or JACE controllers?
Depends on the project. For small to mid-sized jobs focused on protocol conversion, data aggregation and edge integration, the EG71 is a genuine alternative, and a simpler, lower cost one.
For large-scale BMS projects built around Niagara’s native controller libraries or established JACE workflows, it won’t cover the full function set. In those cases, the EG71 works best as an edge integration layer: connecting field devices and forwarding data to Niagara, your BMS, SCADA or cloud platform, rather than replacing the controller outright.
Is there an API to read all EG71 data points?
Not a standard RESTful API for full data point access. Most integrations instead use:
- MQTT or HTTP for active forwarding
- BACnet/IP or Modbus TCP for BMS/SCADA polling
- Node-RED for I/O control logic
If your project needs direct API level access, get in touch and we’ll confirm the current options with Milesight.
What certifications does the EG71 have?
CE, CE RED and FCC. BTL and KNX certification haven’t been obtained yet. If you need security testing documentation or have project-specific compliance requirements, contact OneTemp and we’ll source the latest from Milesight.
Can the EG71 run a lightweight mini BMS or custom dashboard?
Yes. It collects data from wired and LoRaWAN® devices, runs local logic through Node-RED or Python, and forwards it to an HMI, dashboard or upper-level platform via MQTT or HTTP. It also supports Docker for local application deployment.
The EG71 doesn’t include a visualisation front end itself, so dashboarding needs to sit in an upper-level platform such as OneTemp IoT Cloud, a BMS, or a custom application.
Can the EG71 be used for HVAC integration and control?
Yes, provided the HVAC equipment has a compatible communication interface:
- BACnet, common in building automation systems
- Modbus, often used for inverters, heat pumps and controllers
- I/O signals such as dry contacts and analog inputs
- MQTT/HTTP for compatible smart HVAC devices
For VRV/VRF or split systems, check compatibility first. These often run vendor-specific protocols, so confirm whether your equipment supports BACnet, Modbus, I/O control or a compatible open API before specifying.
Milesight EG71 Building IoT Gateway
$1,949.00 ex GST AUD
The Milesight EG71 Building IoT Gateway unifies LoRaWAN®, Modbus, BACnet, KNX and M-Bus devices in a single gateway. Built-in edge computing processes data locally, cutting cloud reliance and response times. With Ethernet, 4G, RS485 and digital I/O, it’s built for HVAC, energy and lighting control.