OVERVIEW
Measure airflow and pressure with the CP210-R
Kimo’s CP 210-R measures air velocity, airflow & pressure and is ideal for use in industrial and pharmaceutical applications
Features
- 0-5/10 V or 0/4-20 mA outputs
- Two relays
- Quick and easy mounting with the 1/4 turn system with wall-mount plate
- Deux sorties relais
- Automatic autozero
- Trend indicator
- “¼ turn” system mounting with wall-mount plate
- Configurable intermediate ranges
- Input Pt100 on terminal block for temperature measurement, range from -100 to +400°C (probes as option)
This unit is available in
- Measuring range:
- CP 211: -100 to +100 Pa
- CP 212: -1,000 to +1,000 Pa
- CP 213: -10,000 to +10,000 Pa
- Power supply 24 Vdc/Vac or 100-240 Vac
- Solenoid valve for auto-calibration (CP211/212)
- With or woithout display
-
SPECIFICATIONS
General Features
Power supply 24 Vac / Vdc ±10%
100-240 Vac, 50-60 Hz
Warning: risk of electric shockOutput 2 x 4-20 mA or 2 x 0-20 mA or 2 x 0-5 V or 2 x 0-10 V (4 wires)
Common mode voltage <30 vac=”” br=””>Maximum load: 500 Ohms (0/4-20 mA)
Minimum load: 1 K Ohms (0-5/10 V)Relay outputs 2 changeover relays
NO: 5A / NC: 3A / 240 VacGalvanic Isolation Inputs and outputs (100-240 Vac models)
Device fully protected by
DOUBLE ISOLATION or REINFORCED ISOLATION
Outputs (24 Vac/Vdc models)Consumption CP210-B: 6 VA / CP210-H: 8 VA Electrical Connection Screw terminal block for cables 2.5 mm2. Carried out according
to the code of good practicePC communication USB-Mini Din cable Environment Air and neutral gases Autozero Manual by push-button; Automatic by solenoid valve
(only CP211/CP212)Type of fluid Air and neutral gases Conditions of use (°C/%RH/m) From -10 to +50°C. In non-condensing condition.
From 0 to 2000 m.Storage Temperature From -10 to +70°C Security Protection class II; Pollution degree 2;
Overvoltage category 2 (OVCII)European directives 2014/30/EU EMC; 2014/35/EU Low Voltage;
2011/65/EU RoHS II; 2012/19/EU WEEEHousing Features
Material ABS V0 according to UL94 Protection IP65 Display 75 x 40 mm, LCD 19 digits 2 lines
Height of digits:
Values: 10 mm; Units: 5 mmConnection Ribbed Ø6.2 mm (CP211/212/213) Pass-through For cables Ø6 mm maximum Cable gland For cables Ø8 mm maximum Weight 340g Configurable intermediate or centre zero ranges
Transmitters Pressure Range Air Velocity Range* CP211 -100/+100 Pa From 3 to 10 m/s CP212 -1000/+1000 Pa From 3 to 30 m/s CP213 -10 000/+10 000 Pa From 3 to 85 m/s *These air velocity ranges are given for information, based on a L type Pitot tube and do not take into account temperature compensation.