OVERVIEW
The 2100-M is used extensively in industrial plants, with proven reliability and accuracy. It comes complete and ready to operate in a compact DIN rail mount enclosure.
The 2100-M (previously the EXPO-3) can multiplex up to 16 analogue inputs, into one input of a PLC or a Data Logging System. It uses solid state switches, making it extremely reliable and durable.
The 2100-M is widely used to expand up inputs on the 2400-A16 and 2100-A16, plus give economic easy accurate analogue input expansion on a PLC.
The PLC only requires two digital outputs and one analogue input to select and receive data from the 2100-M. For each additional 2100-M added to the system, only one more analogue input is required. (The typical fan-out for most PLC’s is up to eight 2100-M’s)
The 2100-M-I and the 2100-M-R are on board input span programmable. The output can be configured to a selection of industry standard output signals.
Features:
- 16 Channel Multiplexer
- Field Programmable Inputs
- Field Programmable Output
- Input Types Available:
- RTD Pt100 (-200~600°C) / (-330~1100°F)
- MilliAmp (4~20 / 0~20mA)
- Clock/Reset Channel Selection, or Binary Channel Selection
- High Accuracy 0.1%
- Compact DIN Rail Mount Enclosure
- Easy to Install
- Solid State Switches for Reliability
Note: The 2100 Series has now been superseded by the 2400 Series. Click Here
2100 is still available however not stocked in Australia (please note; the 2100-L is no longer available) -
SPECIFICATIONS
TYPE
2100-M
General Specifications: (Unless otherwise stated in other input specifications.)
Accurate to <±0.1% FSO Typical Linearity & Repeatability <±0.1% FSO Typical Channel Separation <±0.1% FSO Typical Ambient Drift <±0.01%/C FSO Typical RF Immunity <±1% Effect FSO Typical Operating Temperature 0~60°C Storage Temperature -20~80°C Operating Humidity 5~85%RH Max, Non-Condensing Housing -Material ABS Inflammability V0 (UL94) -Dimensions L=195 W=120 H=70mm -Mounting 35mm Symmetrical Mounting Rail -Weight 700g. Includes Packaging 2100-M-R, 3-wire RTD Inputs
Inputs 16 Single Ended RTD Inputs. All 2nd ‘B’ Terminals Connected RTD Type 3 Wire Pt100 RTD DIN 43760:1980 Standard Input
Other RTD input types available on request (eg Ni100, Cu10, etc.)Ranging Field Programmable Within -200°C to 600°C Minimum Range = 20°C Sensor current 1mA Multiplexed Lead resistance 5Ω/Lead Maximum Recommended
All temperature probes must be isolated from each other and earthSensor Fail -Upscale: >110%FSO (Load Dependant) -Downscale: ≤1%FSO Typical 2100-M-I, mA Inputs
Inputs 16 Single Ended Inputs All -Ve Terminals Connected Ranging Field Programmable Within 0 to 20mAdc Minimum Range = 2mA Input Resistance 100Ω Maximum Over-range 35mAdc Continuous