OVERVIEW
- Input to Output Isolation 300Vac.
- High Accuracy 0.03%.
- Reverse Polarity Protected.
- Compact DIN Rail Mount Enclosure.
- Available with 1, 2 or 4 Transmitters per Enclosure.
- Easy to Install.
- Low Cost.
Dual Output Signal Isolators:
Use the XID-L2 dual channel model. Wire the 4~20mA input in series through both inputs on the transmitter, and the 2 outputs are totally isolated. The outputs are loop powered so you need a separate 24Vdc power supply for each channel.
-
SPECIFICATIONS
Input 4~20mA (up to 4 channels). Input Resistance 50Ω. Output 2 wire 4~20mA (Loop Powered). Output Load Resistance 875Ω @ 24Vdc. (50Ω/V above 6.5Vdc.) Power Supply 24Vdc Nominal (28Vdc Max). Input Voltage Protection 30Vdc. EMC Emissions Compliance EN 61326-1. Safety Compliance EN 61010-1. Accurate to <±0.03% of span typical. Linearity & Repeatability <±0.03% of span typical. Ambient Drift <±0.01%/°C of span typical. R.F. Immunity <0.5% Effect of span typical. Isolation Test Voltages Between Input and Output: 300Vac. Between the separate XID-L transmitters: 300Vac. Response Time <2msec (From 0~90%, 100~10%). Operating Temperature -20~70°C. Storage Temperature -20~85°C. Operating Humidity 5~85%RH Max. Non-Condensing. Mounting 35mm Symmetrical Mounting Rail. Dimensions H=90, W=12.5, D=112mm.
Intech XID-L – Loop Powered Isolators
$294.00 – $806.00 ex GST
Isolating 4~20mA Input to 4~20mA Output Loop Powered Transmitter. 12.5mm Wide!