Demand on data centres and server rooms keeps climbing, and cooling is one of the biggest costs of running them. Most sites rely on the building management system (BMS) or the cooling units themselves to confirm conditions are on target.
The system that controls the cooling is often also the main source of evidence that it’s working. And it usually measures at the return air, not where your equipment draws air in. If the readings say all is well, there’s usually nothing to tell you otherwise, until equipment slows down, alarms appear or energy use tells a different story.
An independent set of data loggers fixes that. It doesn’t replace the BMS, commissioning or airflow modelling. It gives you a second source of truth to check them against.
What the BMS misses
BMS and cooling sensors are typically mounted at the return air or on the cooling units. That tells you what the cooling system sees, which isn’t always what the equipment sees.
- Hotspots inside racks. Air that’s fine at the unit can be several degrees warmer at the top of a rack, at the end of a row, or behind a cluster of new high-density kit.
- Bypass and recirculation. Gaps in blanking panels, missing grommets and open floor tiles let hot and cold air mix, so racks draw in warmer air than you think.
- Overcooling. The flip side. Some zones run far colder than they need to, often because setpoints were lowered to fix a hotspot elsewhere. That’s energy spent with no added protection, and very cold air can cause condensation on nearby surfaces.
- Drift over time. Layouts change, equipment gets added and airflow shifts. A room that was balanced at commissioning may not be today.
What to measure
Temperature at the rack inlet matters most, because that’s the air your equipment actually draws in. ASHRAE’s recommended envelope for air-cooled IT equipment (Classes A1 to A4) is 18 to 27°C, measured at the equipment inlet. Check your hardware manufacturer’s limits as well.
Humidity is the second measure. Air that’s too dry raises the risk of static discharge. Too much moisture, or surfaces that get too cold, risks condensation, particularly near cooling coils. ASHRAE sets humidity limits to manage both risks, so logging temperature and relative humidity together lets you track them.
Where to put loggers
You don’t need a sensor on every server. Well-placed loggers tell you most of what you need to know, and high-density or mixed-equipment rooms will need more coverage, especially at rack tops and row ends.
- Rack inlets: top, middle and bottom. Temperatures often rise with height, so one reading per rack can hide the problem. Start with racks at row ends, high-density racks and any near known problem areas.
- Cold aisle and hot aisle. Comparing the two confirms your containment is working. A small difference between them points to air mixing.
- Next to the cooling units. Place a logger near the BMS or unit sensor so you can compare readings directly.
- Anywhere that’s changed. New equipment, a moved rack or a recent fit-out are all worth watching for a few weeks.
Run the loggers for at least a couple of weeks to capture normal load patterns, longer if your load or the weather varies a lot. Then compare their data with what the BMS reported over the same period.
For sites where IT security limits what can connect to the network, cellular-equipped RX3000 models can upload independently of the building’s systems, subject to mobile coverage. That also makes them a true second source.
Turning data into action
With independent data in hand, you can act on what it shows.
- Fix hotspots. Adding blanking panels, tidying cabling and adjusting tile placement or rack layout often fix more than lowering the setpoint. Make one change at a time and re-check the rack inlets.
- Cut energy. Where zones are overcooled, you can raise setpoints in small steps and confirm with your loggers that inlets stay in range.
- Keep records. A logged history supports audits, SLAs with customers or tenants, and the business case for a cooling upgrade.
Trust the system, then check it
Your BMS isn’t wrong. It just can’t see everything. A small set of standalone loggers gives you an independent view of what your equipment is actually breathing, and the records to act on it.
Want to go deeper? Watch Onset’s webinar on wireless monitoring for data centre cooling to learn more.
From a single server room to a multi-room facility, we’ll help you pick the right loggers and get them in place.