OVERVIEW
The GDA 3100 has a configurable analog output of 4-20 mA; 0-20 mA; 0-5 V; 0-10 V and a volt free relay which can be user programmed to operate anywhere within the sensor range. The unit is powered from 24 VDC.
- Standalone system or 4-20 mA o/p sensor or both
- User definable alarm point (relay operation)
- 1 SPCO alarm relay (volt free)
- User selectable 4-20 mA or 0-20 mA 0-5 V 0-10 V o/p
- 24 VDC operation
- Robust housing
- Immune to changes in humidity and temperature
- Easy to install
- Calibration required every 3 years with 6 monthly functional tests
- Australian Factory Certificate of Calibration
Made in Australia and Supported in Australia
Refrigerant Gases
Refrigerant gases are used to provide a means of cooling the evaporators in freezers and air conditioning for plant rooms and chiller plants. Historically CFC refrigerant gases such as R11, R12 and R22 have been used. CFC’s are ozone depleting gases and are now being phased out and replaced by ozone friendly gases such as R134, R407 and R410.
Why is there a need to detect them?
- All these gases are toxic at relatively low levels. Prolonged exposure to these gases is hazardous and results in serious health risks. GDA sensors can detect these gases at very low levels, in order to prevent this hazard becoming a danger to life.
- Air conditioning systems and chillers that are leaking their refrigerant gases are not performing to maximum efficiency. The major use of refrigerant gases is in the re charging of these systems. If leaks are detected early the problem can be alleviated much quicker, saving costs on replacement gas, co maintenance and protecting the environment.
- Gas detection at low levels (part per million) will give an early warning of leakage, therefore safeguarding life and maintaining the efficiency of the plant.
Gas Detection Australia has a range of ultra-low level refrigerant gas leak detection systems specifically developed to prevent the expensive results of refrigerant gas leaks for R22, R123, R134a, R404, R407, R410, R514a, R1234yf and many others.
Meets the requirements of AS/NZS 5149.3:2016 and ISO 5149-3:2014
Safe Work Australia Exposure Standards
R134a (1, 1, 1, 2-Tetrafluoroethane) 8 Hour Time Weighted Average
1000 ppm
15 Minute Short Term Exposure Limit
-
More Infomation © Commonwealth of Australia 2018
-
APPLICATIONS
Refrigerant Plant Monitoring
Refrigerant gases are used to provide a means of cooling the evaporators in freezers and air conditioning for plant rooms and chiller plants. Historically CFC refrigerant gases such as R11, R12 and R22 have been used. CFC’s are ozone depleting gases and are now being phased out and replaced by ozone friendly gases such as R134, R407 and R410.
Why is there a need to detect them?
All these gases are toxic at relatively low levels. Prolonged exposure to these gases is hazardous and results in serious health risks. GDA sensors can detect these gases at very low levels, in order to prevent this hazard becoming a danger to life.
Air conditioning systems and chillers that are leaking their refrigerant gases are not performing to maximum efficiency. The major use of refrigerant gases is in the re charging of these systems. If leaks are detected early the problem can be alleviated much quicker, saving costs on replacement gas, co maintenance and protecting the environment.
Gas detection at low levels (part per million) will give an early warning of leakage, therefore safeguarding life and maintaining the efficiency of the plant.
Gas Detection Australia has a range of ultra-low level refrigerant gas leak detection systems specifically developed to prevent the expensive results of refrigerant gas leaks for R22, R123, R134a, R404, R407, R410, R514a, R1234yf and many others.Meets the requirements of AS/NZS 5149.3:2016 and ISO 5149-3:2014
Air Conditioning Monitoring
Air conditioning gas detection systems are used in a number of ways. In air conditioning plant rooms Gas Detection Australia has gas sensors and gas detectors for Ammonia , Propane, CO2 and R134a, R123, R125, R404, R407c R410a etc. In enclosed laboratories classrooms and workspaces. The Gas Detection Australia range of flush mounted Air Conditioning gas sensors for Carbon Dioxide GDA 4360 are used by the HVAC industry to control fresh air input into rooms and modulate supply. In the case of VRF systems needing room air conditioning gas detection HVAC industry uses the flush mounted GDA 3160 which are unobtrusive and used to detect low levels of R134a, R123, R404, R407c, R410 etc.
Meets the requirements of AS/NZS 5149.3:2016 and ISO 5149-3:2014
Designed, Manufactured and Supported in Australia.
-
SPECIFICATIONS
Detectable Gases Refrigerant Gas (See Ordering Information) Power Requirements 24 VDC Output Types 0-20 mA, 4-20 mA, 0-5 V, 0-10 V (4-20 mA Default) Output Specifications 4-20 mA max 1K at 24 VDC supply (4-20 mA); Voltage: i/p Z for voltage o/p options 10K > Relay NC NO Comm. 1A at 24 VAC Power Consumption <300 mw=”” average=”” td=””> Connection 4 pin plug connector and 3 screw down Relay contacts NC, NO, Comm (volt free) Wiring 3 core cable with overall screen, Screen to be connnected to earth at control unit end only Operating Temperature -20 to 40°C (applications below 5°C low temperature version required Order No. 3100-0x-LT) Operating Humidity 5% to 95% RH peak non condensing Accuracy of Reading 1% Full scale Warm Up Time <2 minutes=”” sensor=”” accurate=”” after:=”” 30=”” td=””> Response Time Approx. 30secs Zero Drift ≤2% Full scale p.a Calibration Drift ≤2% Full Scale p.a Sensor Technology Non Dispersive Infra-Red (NDIR), Dual Wavelength Calibration Requirement Every 3 years if sensor operated at SATP with 6 monthly functional tests if required. Typical Operating Life 7 years in standard operating environment Warranty 24 months from date of dispatch Dimensions 115 x 130 x 71 mm (L, W, D) Mounting holes 105 x 75 mm Enclosure Material ABS Plastic Cable Entry User provided
GDA 3100 – Refrigerant Gas Detector
$0.00 ex GST
The GDA 3100 Refrigerant Gas Detector uses the latest in NDIR techniques for detecting a wide range of refrigerant gases and is immune from cross sensitivity to other gases