PM8AO - 8 Current Output Module

Manufacturer:
The PM8AO is a 8 channel current output module. Each channel can be set to output a current in the range 0 – 20mA.
Part Number: PM8AO
Back to Previous Page
Product Files
$292.00 ex GST
i h

PM8AO - 8 Current Output Module

The PM8AO is a 8 channel current output module. Each channel can be set to output a current in the range 0 – 20mA. The outputs are isolated from the logic and share a common negative terminal.

The resolution is 12 bits, so writing a value to the Modbus register for each output of 0 – 4095 would give an output current of 0 – 20mA. A value of 819 ± 1LSB will give a current output of 4mA.

The module may be used as either a slave or master on the Modbus network. When used with a PC or PLC the module will be configured as a slave. When used with a PM8AI module in a point-to-point configuration, the DIP switch 9 must be turned on to set the module up as a master. In this mode the PM8AO module will automatically read the information from the PM8AI module and write the input status to the outputs.

PM8AO - 8 Current Output Module

Analog Outputs 8
Current 0-20mAdc
Offset (switch selectable) 4mA
Resolution 12 bit (0-4095)
Drift 100 ppm/deg.C typ.
Accuracy 0.05 % of span
Load (max) 1000 Ohms @24Vdc
Isolation (Field & Logic) 1500VAC RMS
Power supply (Field) +24Vdc

Order Codes

  • PM8AO - PROMUX 8 Current Output Module

PM8AO - 8 Current Output Module

The PM8AO is a 8 channel current output module. Each channel can be set to output a current in the range 0 – 20mA. The outputs are isolated from the logic and share a common negative terminal.

The resolution is 12 bits, so writing a value to the Modbus register for each output of 0 – 4095 would give an output current of 0 – 20mA. A value of 819 ± 1LSB will give a current output of 4mA.

The module may be used as either a slave or master on the Modbus network. When used with a PC or PLC the module will be configured as a slave. When used with a PM8AI module in a point-to-point configuration, the DIP switch 9 must be turned on to set the module up as a master. In this mode the PM8AO module will automatically read the information from the PM8AI module and write the input status to the outputs.