Search
Menu Close

Monnit Enterprise Pulse Counter Wireless Sensor

Manufacturer:
The Monnit Enterprise Pulse counter can be connected to monitor an item's usage, frequency, or actuations. The collected data can be used to improve service or protect productivity.
Part Number: MNS2-4-W2-PC-01
Back to Previous Page
$359.00 ex GST
i h

Counts pulses & sends real time alerts via SMS text or email


The Monnit Enterprise Pulse counter is ideal for typical commercial and enterprise environments. It can be connected to the pulse output of a system (water meter, power met, etc.) to count the number if actuations within a given time frame or aggregate pulses in an ongoing accumulation. The device is capable of counting passive (open/closed switch) and active (up to +15 VDC) pulses and can count the positive edge, negative edge or both edges of a pulse.

The counter includes 3 software configurable low pass filter settings (No filter, 40 Hz filter, or 4 Hz filter) and can filter pulses with pulse widths greater than those designated in the technical specifications. For example, if the 4Hz filter is set, the pulse counter will count a pulse if its width is longer than 250 ms, if its width is shorter than 250 ms it will be completely or partially filtered. 

The sensor can be programmed to send an alert through the iMonnit Online Sensor Monitoring and Notification System when a given number of pulses have been reached within a set time frame. These alerts from the iMonnit system are sent in real time via SMS text or email.

The pulse counter comes standard with two replaceable 1.5V AA batteries. It is also available with a line power option1. This option includes a barrel power connector allowing it to be powered by a standard 3.0-3.6V power supply and uses two standard 1.5V AA batteries as backup for uninterrupted operation in the event of line power outage.


Features

  • Impressive wireless range of up to 1,200 feet through walls
  • Frequency-hopping spread spectrum (FHSS)
  • Improved interference immunity
  • Improved power management for longer battery life
  • Encrypt-RF® Security (Diffie-Hellman Key Exchange + AES-128 CBC for sensor data messages)
  • Stores 2000 to 4000 readings if gateway connection is lost (non-volatile flash, persists through the power cycle)
    • 10-minute heartbeats = ~ 22 days
    • 2-hour heartbeats = ~ 266 days
  • Over-the-air updates
  • Free iMonnit basic online wireless sensor monitoring and notification system to configure sensors, view data and set alerts via SMS text and email


Applications

  • Water, gas and air flow meters
  • Door access counter
  • Turn style counting
  • Forklift swat switches
  • Button or switch integration
  • Product line tracking


IMPORTANT - Sensor Operation

Please note: this sensor requires both an applicable Gateway and iMonnit software to operate. For further information, please refer to the tabs above or related products below.



1This option must be selected at time of purchase as the internal hardware of the sensor must be changed to support the selected power requirements by the manufacturer. 

Monnit Gateway Options

An integral component of any IoT network is the gateway. A gateway device allows for data from sensors to be transmitted to the iMonnit software platform.


Monnit Ethernet Wireless Gateway 4

Monnit’s Ethernet Gateways allow your Monnit Wireless Sensors to communicate with the iMonnit™ Online Wireless Sensor Monitoring and Notification System without the need for a PC. Simply provide power and plug the gateway into an open Ethernet network port with an internet connection. It will then automatically connect with our online servers, providing the perfect solution for commercial locations where there is an active internet connection.

Learn more about the Ethernet Wireless Gateway 4>>



Monnit 4G + Ethernet IoT Gateway

The ALTA® by Monnit Wireless IoT Gateway combines a 4G LTE CAT-M1/NB2 cellular engine and Ethernet platform with Monnit’s wireless access point network to aggregate and communicate data from Monnit ALTA Wireless Sensors. The ALTA IoT Gateway allows ALTA Sensors to operate on the world’s leading cellular networks and stay connected to the Internet. The gateway uses AC main power but also has redundant power through a battery backup lasting up to 60 hours.

To meet the global demand for enterprise IoT deployment, the IoT Gateway communicates with the cloud-based iMonnit® monitoring software via cellular transmission, making it ideal for remote locations or where the Internet isn’t available. The RJ-45 Ethernet jack allows local device configuration, diagnostics, and connectivity backup. The IoT Gateway is instrumental in sending sensor notifications via text, email, or call if user-defined conditions are met or exceeded.

Learn more about the 4G + Ethernet Wireless Gateway 4>>


Online Sensor Monitoring Software

iMonnit is a cloud based mobile internet platform and central hub for managing Monnit and ALTA products. All data is secured on dedicated servers operating Microsoft SQL Server. This online user interface is where all your device settings can be arranged, supervised, and modified to reflect your unique environment. OneTemp will look after the activation and setup of your new online iMonnit account free of charge. There is also a free mobile app for you to stay in control at all times. Start with the basic version or upgrade to iMonnit Premiere to enjoy the full features your Monnit experience can offer.


iMonnit Basic Vs Premiere:

  • Basic - Free with no ongoing costs
    Monnit Basic is included for free with all wireless sensors, providing basic features for you to configure and monitor your sensors online. These basic features only support one network and one registered user on an account.
  • Premiere - Minimal Annual Fee
    iMonnit Premiere allows for enhanced functionality of your wireless sensors and includes an advanced software feature set at a low annual cost. All of iMonnit's advanced features are availble for configuration. You can have more sensors on your account, support multiple users, and view floorplans for all your sensors.

Learn more about the iMonnit Premier Online Software>>

 


Technical Information

Supply voltage 2.0–3.8 VDC (3.0–3.8 VDC using power supply) 1
Current consumption 0.2 μA (sleep mode), 0.7 μA (RTC sleep), 570 μA (MCU idle),
2.5 mA (MCU active), 5.5 mA (radio RX mode),
22.6 mA (radio TX mode)
Operating temperature range (board circuitry and batteries) -18°C to 55°C (0°F to 130°F) using alkaline
-40°C to 85°C (-40°F to 185°F) using lithium 2
Optimal battery temperature range (AA) +10°C to +50°C (+50°F to +122°F)
Maximum count 4294967296 (32 bit number)
Input voltage 0 to 15 Volts DC
Detection wires High impedance (2-wire), 3 ft length
Counter operation Positive and/or negative edge pulses
Compatibility Open collector NPN switches (passive)
Mechanical switches (passive)
0–15V driven source (active) 3
Max input pulse rate/min pulse width with passive input 4


Max Pulse Rate Min Pulse Width 5
No Filter ~ 2 KHz ~ 0.5 ms
4 Hz Filter ~ 4 Hz ~ 250 ms
40 Hz Filter ~ 40 Hz ~ 25 ms
Datalogging Datalogs 2000 to 4000 readings if gateway connection is lost (non-volatile flash, persists through the power cycle):
-10-minute heartbeats = ~ 22 days-2-hour heartbeats = ~ 266 days
Wireless range 1,200+ ft non-line-of-sight
Security Encrypt-RF® (256-bit key exchange and AES-128 CTR)
Weight 0.7 ounces
Certifications 900 MHz product; FCC ID: ZTL-G2SC1 and IC: 9794A-G2SC1. 868 and 433 MHz product tested and found to comply with: EN 300 220-2 V3.1.1 (2017-02), EN 300 220-2 V3.1.1 (2017-02) and EN 60950


1 Hardware cannot withstand negative voltage. Take care when connecting a power device.
2 At temperatures above 100°C, it is possible for the board circuitry to lose programmed memory.
3 Low Pulse: 0 Volts to 0.2 * VBatt, High Pulse: 0.8 * VBatt to 15 Volts.
4 High pulse count rates can impact battery life. AA battery powered sensors are recommended if counting pulses faster than 1x per second.
5 Input pulse rate must be less than specified Max Pulse Rate and input pulse width must be greater than specified Min Pulse Width to ensurethe input pulse is counted.

Counts pulses & sends real time alerts via SMS text or email


The Monnit Enterprise Pulse counter is ideal for typical commercial and enterprise environments. It can be connected to the pulse output of a system (water meter, power met, etc.) to count the number if actuations within a given time frame or aggregate pulses in an ongoing accumulation. The device is capable of counting passive (open/closed switch) and active (up to +15 VDC) pulses and can count the positive edge, negative edge or both edges of a pulse.

The counter includes 3 software configurable low pass filter settings (No filter, 40 Hz filter, or 4 Hz filter) and can filter pulses with pulse widths greater than those designated in the technical specifications. For example, if the 4Hz filter is set, the pulse counter will count a pulse if its width is longer than 250 ms, if its width is shorter than 250 ms it will be completely or partially filtered. 

The sensor can be programmed to send an alert through the iMonnit Online Sensor Monitoring and Notification System when a given number of pulses have been reached within a set time frame. These alerts from the iMonnit system are sent in real time via SMS text or email.

The pulse counter comes standard with two replaceable 1.5V AA batteries. It is also available with a line power option1. This option includes a barrel power connector allowing it to be powered by a standard 3.0-3.6V power supply and uses two standard 1.5V AA batteries as backup for uninterrupted operation in the event of line power outage.


Features

  • Impressive wireless range of up to 1,200 feet through walls
  • Frequency-hopping spread spectrum (FHSS)
  • Improved interference immunity
  • Improved power management for longer battery life
  • Encrypt-RF® Security (Diffie-Hellman Key Exchange + AES-128 CBC for sensor data messages)
  • Stores 2000 to 4000 readings if gateway connection is lost (non-volatile flash, persists through the power cycle)
    • 10-minute heartbeats = ~ 22 days
    • 2-hour heartbeats = ~ 266 days
  • Over-the-air updates
  • Free iMonnit basic online wireless sensor monitoring and notification system to configure sensors, view data and set alerts via SMS text and email


Applications

  • Water, gas and air flow meters
  • Door access counter
  • Turn style counting
  • Forklift swat switches
  • Button or switch integration
  • Product line tracking


IMPORTANT - Sensor Operation

Please note: this sensor requires both an applicable Gateway and iMonnit software to operate. For further information, please refer to the tabs above or related products below.



1This option must be selected at time of purchase as the internal hardware of the sensor must be changed to support the selected power requirements by the manufacturer. 