Measuring inputs |
Up to 8 user configurable analog inputs for: RTD temperature probes; resistance transmitters; thermocouples; current 0(4) to 20 mA; voltage 0(2) to 10 V; heater current, C-level control; customer-specific linearization possible |
Digital inputs |
6 digital inputs for potential-free contacts |
Outputs |
Max. 6 slots for the following plug-in cards: 2 relays (normally open contact); 1 relay (changeover contact); 2 logic outputs 0/5 V; 1 logic output 0/22 V; 1 solid state relay; 1 analog output; 1 voltage supply for two-wire transmitter via 22 V logic output |
Additional contacts |
Up to 2 external relay modules with 8 changeover contacts or 8 logic outputs 0/12 V |
Interfaces/protocols |
1 × RS422/485 (Modbus); 1 × PROFIBUS DP or RS422/485 (Modbus); setup interface |
Number of control channels |
Up to 8 independent and user configurable control channels |
Controller structure |
P; I; PD; PI; PID (2 sets of control parameters per channel) |
Controller type |
Two-state controller; three-state controller; modulating controller; continuous controller; continuous controller with integrated position controller |
Program controller |
50 programs each with up to 100 sections; max. total of 1000 sections, 16 control tracks |
Alarms |
16 limit value monitoring functions, each with 8 selectable alarm functions with timer and confirmation functions |
Display |
5-inch TFT color screen (320 × 420 pixels, 27 colors); plain text display available in English, German, French, and other languages; process-specific texts and screens individually configured; bar graph display |
Mounting |
Panel mounting |
Protection type |
At the front IP65; at the rear IP20 |
Voltage supply |
AC 110 to 240 V +10/-15 %, 48 to 63 Hz; AC/DC 20 to 30 V, 48 to 63 Hz |
Format |
144 mm × 130 mm × 170 mm, installation dimensions 92 mm × 92 mm |
Special features |
Modular structure with plug-in cards that can be retrofitted individually; easy-to-use PC setup program including startup software; recording function with evaluation software; min. sampling rate 50 ms; autotuning procedure for determining the controller parameters; programmable operating level; math and logic functions; programmable function keys and individually configured process screen for plant visualization; teleservice and email notification (via external modem) |
Approvals |
cULus |