Looking for a DATA LOGGER? Now see – www.hobodataloggers.com.au

Shimaden PAC18 Single Phase Thyristor Power Regulator

A PAC18 is a Thyristor for smooth, fast switching of power loads for ultimate control.
Part Number: PAC18
Call for pricing

As a succession device for the PAC15 and PAC16 Series which achieved a record
of long-term durability and reliance, the PAC18 Series thyristor power
regulator pursues an even higher level of functionality and safety.

Features:

  • Easy Front Key Setting
  • A 7-segment LED displays input and output values and various other parameters.
  • Slow-Up, Slow-Down Function
  • Output Current Detection Function (Optional)
  • Parameter Setting Function (Optional)
  • Universal Power Supply (100 ~ 240 V AC)
  • Automatic Frequency Function (50/60 Hz)

Functions:

  • Automatic detection of power frequency 50/60 Hz
  • Control circuit power supply is 100 V ~ 240 V common: this corresponds to a wide power/voltage range.
  • Output current detection function (optional) available, adaptable to overcurrent protection, current limit function and alarm output function (power failure, overcurrent, heater break detection and hardware error)

Note: A power filter is used in conjunction with the Tyristor for CE Compliance. See brochure

As a succession device for the PAC15 and PAC16 Series which achieved a record
of long-term durability and reliance, the PAC18 Series thyristor power
regulator pursues an even higher level of functionality and safety.

Features:

  • Easy Front Key Setting
  • A 7-segment LED displays input and output values and various other parameters.
  • Slow-Up, Slow-Down Function
  • Output Current Detection Function (Optional)
  • Parameter Setting Function (Optional)
  • Universal Power Supply (100 ~ 240 V AC)
  • Automatic Frequency Function (50/60 Hz)

Functions:

  • Automatic detection of power frequency 50/60 Hz
  • Control circuit power supply is 100 V ~ 240 V common: this corresponds to a wide power/voltage range.
  • Output current detection function (optional) available, adaptable to overcurrent protection, current limit function and alarm output function (power failure, overcurrent, heater break detection and hardware error)

Note: A power filter is used in conjunction with the Tyristor for CE Compliance. See brochure

  • Control element configuration : Thyristor x 2 inverse-parallel connection
  • Main/control power supply : 100 ~ 240 V AC, 5 VA (main/control power supply used in the same phase)
  • Voltage fluctuation tolerance : Max. ±10% of rated voltage
  • Rated frequency : 50/60 Hz
  • Rated current : Any one of 6 types (20, 30, 45, 60, 80, 100 A)
  • Control output range : 0 ~ 97% or more
  • Applicable load : Resistance load or inductive load (transformer primary control: phase control or complex control)
  • Control type : Phase control, cycle calculation zero voltage switching control, complex control (specify when ordering)(No output feedback function) 
    P: Phase control (specify when ordering); phase angle proportional output, voltage proportionaloutput or voltage square proportional output
    C1: Cycle calculation zero voltage switching control
    X1: Complex control (phase control when output increases from 0%, followed by cycle calculation zero voltage switching control)
  • Cooling : Self cooling
  • Protection :
    1) Electronic overcurrent gate cutoff circuit (optional); alarm output when operating, detection by current transformer (CT)
    2) External rapid fuse (sold separately)
    3) Hardware error detection (optional); detects short circuit or thyristor shorting when output is 0%.
  • Control input : Current: 4 ~ 20 mA DC [receiving impedance 100Ω] common with contact Voltage: 1 ~ 5 V, 0 ~ 10 V DC [input resistance approx. 200kΩ] common with contact
  • Standard functions
    External adjustment function : External adjusters such as ramp lower limit, ramp upper limit, current limiter and manual can be connected.
    Up to 3 external adjusters can be used. B characteristics 10kΩ 3 lines
    External adjusters sold separately
    Variation limit : 0.0 ~ 99.9 sec. variable setting (set by front surface key switch) (slow-up, slow-down) Time required to reach 0 ~ 100% output